EC Plug Fan Retrofit Saves 50 Percent Energy In Commercial Building
Approximately 50% of energy could be saved by replacing the existing AC belt driven backward-curved fans throughout a building with EC Plug Fans. A retrofitting project in the government-owned Wakefield Building in Adelaide achieved great energy-savings and performance increases.
Melbourne, VIC, Australia, January 31, 2012 - (PressReleasePoint) - Fan energy is typically the most significant consumer of energy within a commercial building. Approximately 50% of energy can be saved by replacing the existing AC belt driven backward-curved fans throughout a building with EC Plug Fans.
Wakefield House Building, Adelaide
The original fan and air handling unit (AHU) arrangement for level 14, which is typical throughout all floors of the building, comprises a coil face bypass arrangement, with air distributed via a belt driven backward curved centrifugal fan arrangement.
In October 2011, the existing fan was replaced by an ebm-papst EC Plug Fan. Minor works to the damper were also performed. The project was managed by System Solutions Engineering Pty Ltd, an engineering firm and consultancy based in Adelaide.
The main issues with the arrangement and system related to performance and the ability to adequately distribute the air to the floor. Due to the system type and the fans proximity to the cooling coil, cooling capacity of the AHU is reduced as only part of the coil face is utilised. Air from the fan is only incident on part of the cooling coil, which then is reflected by insufficient capacity being delivered to the floor.
Contributing to the insufficient capacity is the reduction in supply air to deliver cooling to the floor. Locating the fan so close to the cooling coil creates turbulence and increases the system static, which in turn reduces the supply air quantity by approximately 10-15% from design. When combined with the reduced performance of the cooling coil, the net reduction in capacity to the floor is approximately 45% from design.
Old fan current
Starting currents for each day, which exceed 80 Amps, whereas the average current across the phases throughout daily fan operation is 8.55 Amps.
New system
In October 2011, the existing centrifugal belt driven fan was replaced with an EC Plug fan. Minor works to the damper arrangement and operation were also performed.
The new EC Plug Fan was installed away from the cooling coil, and the damper was rearranged above the cooling coil in the bypass ductwork. The new damper was installed to provide an equivalent pressure drop to the cooling coil, which provides more stable distribution and controllability of supply air. The EC Plug Fan pressurises the plenum chamber and rather than delivering an uneven air profile as per a centrifugal fan as indicated in the figure above, provides uniform air pressure and therefore volume across the whole cooling coil, achieving greater capacity from the coil. As part of the upgrade works, airflow was increased by 10% returning the supply air quantity to the design figure and combined with the resultant increased coil efficiency, cooling delivered to the floor was increased by approximately 15-20%.
New fan current
Starting currents now approach 6 Amps (before 80 Amps), and the average current across the phases throughout daily operation of the EC Plug Fan is 4.7 Amps.
Summary - Energy and Operating Cost
Annual savings of
- 9,470.7 kWh
- $1,799.43
- 6.5 tonnes of CO2 Emissions.
For commercial office buildings, up to 70% of the total energy use is attributed to the heating,ventilation, and air conditioning (HVAC) systems. As fan energy is typically the most significant consumer of energy within a commercial building, the reduction of approximately 50% from the replacement of the existing AC belt driven fans throughout the building to EC Plug Fans, will have a significant impact on the total energy consumed, as well as reduction in green house gas emissions.
Watch the video here!
Press Contact:
Caroline Bommes
10 Oxford Road
Laverton North VIC 3026
Australia
03 9360 6400
http://www.ebmpapst.com.au
**r**i**.**m**s@*u.ebmpapst.com
Email partially hidden to block spam. Please use the contact form here.
More User Press Releases
- ECI Drives Modular System Expanded by Adding 42 Mm Variant Motor with User-Selectable Motor, Gearbox and Brakes
- ebm-papst A&NZ MD Simon Bradwell speaker at Pump Industry Australia Breakfast Meeting in Melbourne
- Communication with EC Fans and Modbus Rtu–Hand-Shaking Connections
- New GreenTech EC Compact Axial Fan Impresses with High Efficiency
- Energy-Saving Fans Made of "Epylen" Wood/Plastic Composite Biomaterial - Innovation by ebm-papst
- GreenTech EC Compact Fan Scores In Practical Use - More Power, Less Consumption But Same Size
- No alternative to energy-efficient fans: Controlled home ventilation for new buildings and renovation
Like this site on Facebook
Distribute Press Release
- Post press release to 50+ free press release websites.
- Send to 100+ online publications.
- Effortlessly publish all your press releases with our automated pickup and submission service.
User login
Search
Bookmark/Search this post
Primary Menu
- News by Region
- Business
- List of Industries
- Technology
- Aerospace & Defense
- Agriculture & Forestry
- Arts
- Automotive
- Business Services
- Chemicals
- Construction & Maintenance
- Consumer Goods
- Education
- Electrical & Electronics
- Energy
- Entertainment
- Food & Related Products
- General Business
- Government
- Healthcare
- Heavy Industry
- Home
- Industrial Goods & Services
- Industrial Materials
- Medical
- Mining & Drilling
- Publishing & Printing
- Retail
- Society
- Sports
- Supermarkets
- Telecommunications
- Textiles & Nonwovens
- Transportation & Logistics
- Travel & Hospitality
- Wholesale